Описание

Function Fault annunciator
Alarm inputs 8
Alarm inputs extendable up to 88
Operate delay +
Special features konfigurierbar, busfahig
Width 70 mm
Type RP 5991
Common Alarm Annunciator RP 5990, RP 5991 Fast localisation of failures and their causes Reduction of standstill times in production Common alarm annunciator with manual or auto reset of faults Expandable from 8 to 88 fault signals Open or closed circuit operation settable with rotational switch on base unit and with link X1/X2 on extension units Adjustable on delay for input signals 0 to 10 sec Reset buttons for audible alarm and common alarm on front side Connection for external reset of audible alarm Galvanic separation to bus RS485 (optional) Accessories: buzzer RK 8832, display unit EH 5990, EH 5991 Width: 70 mm Base Module RP 5990:- 8 fault signal inputs with indicator LED on the unit- One relay output each for audible alarm and common alarm- Reset buttons for audible alarm and common alarm- Connection for external reset of audible alarm Extension Module RP 5991:- 8 fault signal inputs with indicator LED on the unit- As option one relay output each for audible alarm and common alarm- As option reset buttons for audible alarm and common alarm''